Model No. |
YSDU40-24 |
DC VOLTAGE RANGE |
21-29 Vdc |
DISCHARGE CURRENT RANGE |
0~40A |
CHARGING CURRENT |
2A |
NORMAL INPUT VOLTAGE |
24Vdc |
INPUT VOLTAGE RANGE |
24~29Vdc |
RATED CURRENT |
40A |
NORMAL BATTERY VOLTAGE |
24Vdc ( 2 x 12Vdc in series or 1 x 24Vdc) |
BATTERY TYPE |
Lead-acid battery |
EXTERNAL BATTERY CAPACITIES |
4AH ~ 135AH |
RELAY CONTACT RATINGS (max.) |
30VDC/1A resistive load |
DC BUS OK |
Relay contact : Short when DC voltage between 21~29V(±2%), relay contacts |
LED(Green) : DC BUS OK : light ; DC BUS fail : dark |
BATTERY FAIL |
Short when battery voltage falls below 22V(±2%) or battery failure is observed through the battery test function, relay contacts |
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery OK : dark |
BATTERY DISCHARGE |
Relay contact : Short when battery in discharge condition, relay contacts |
LED(Yellow) : light : Battery discharging ; dark : Battery is not discharging or discharging current < 1.0A |
Working Temperature |
-30 ~ +70℃ (Refer to “Derating Curve”) |
Withstand Voltage |
IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ; Relay – Chassis : 0.5KVac |
Protection |
Short circuit/Battery reverse polarity/Over discharge current /Battery deep discharge |
Connection |
I/P :4 poles terminal Block O/P: 6 poles terminal Block |